Utilize este identificador para referenciar este registo: https://hdl.handle.net/1822/49853

TítuloAnálise estrutural da Igreja de Nossa Senhora da Conceição
Outro(s) título(s)Structural analysis of the Our Lady of Conception Church
Autor(es)Bueno Cadena, Diana Celina
Orientador(es)Mendes, Nuno Adriano Leite
Viviescas Jaimes, Álvaro
Palavras-chaveConstruções históricas
Alvenaria
Igrejas
Anomalias
Modelação numérica
Historical constructions
Masonry
Church
Damage
Numerical modeling
Data14-Dez-2016
Resumo(s)A Igreja de Nossa Senhora da Conceição, localizada na Vila de Monforte (Portalegre), está classificada como Imóvel de Interesse Público. Esta igreja faz parte de um conjunto de três igrejas (Igreja do Calvário e Igreja de S. João Batista) que formam o triângulo mágicoreligioso de Monforte. Apesar da sua data de construção não ser exatamente conhecida, a documentação existente indica que a Igreja de Nossa Senhora da Conceição poderá ter origem no século XVII. A igreja é constituída pela nave, cabeceira, sacristia e por um corredor de acesso ao púlpito. As paredes foram construídas em alvenaria de pedra irregular e apresentam diferentes espessuras. As paredes possuem também oito contrafortes com diferente geometria. A igreja foi alvo de vários trabalhos de reabilitação, que podem ser agrupados em dois grupos principais de intervenções espaçados de cerca 130 anos: (a) Intervenções realizadas entre 1775 e 1840; (b) Intervenções realizadas em 1973. Durante o primeiro período, e devido às infiltrações das águas pluviais, foram efetuadas pequenas reparações, tais como substituição de telhas. Estes trabalhos foram realizados com recurso a materiais compatíveis com os existentes. No segundo período de intervenções (1973), a Direção Geral dos Edifícios e Monumentos Nacionais (DGEMN) efetuou a reconstrução das coberturas. Atualmente, a igreja não se encontra em uso e apresenta dano severo na abóbada da nave e fendas com severidade moderada nas paredes transversais. O pavimento exterior apresenta dano devido assentamentos do solo. Além do dano estrutural, a igreja apresenta outros tipos de anomalias, tais como manchas de humidade nas abóbadas e na base das paredes de alvenaria, deterioração dos frescos interiores, destacamento do reboco exterior das paredes, deterioração das pinturas exteriores, presença de vegetação e telhas partidas nas coberturas. O presente estudo tem como principal objetivo avaliar o desempenho estrutural da igreja e identificar as principais causas do dano estrutural existente. O trabalho envolveu a preparação e calibração de um modelo de referência e a análise não linear estática para as forças gravíticas. Além disso, consideraram-se três aspetos que podem ter influência no dano da estrutura, nomeadamente, a influência do enchimento nas abóbadas, a influência do esquema estrutural da cobertura e a interação solo-estrutura. O dano foi avaliado com recurso às curvas de capacidade, deslocamentos e extensões principais de tração. Em geral, os resultados obtidos apresentam semelhanças com o padrão de dano da igreja e permitiram verificar que o dano parece estar associado ao impulso das coberturas no topo das paredes de alvenaria e à flexibilidade da parte sul da igreja. No entanto, recomenda-se a realização de trabalhos de diagnóstico, tais como a inspeção das coberturas e ensaios geotécnicos, que permitam validar esta conclusão.
The Our Lady of Conception Church, located in village of Monforte (Portugal), is classified as a Public Interest Building. This church is part of a set of three churches (Calvary Church, the St. John the Baptist Church and the Our Lady of Conception Church), which form the magic-religious triangle of Monforte. Despite its not exactly known construction date, the existing documentation states that the Our Lady of Conception Church may have been constructed in the seventeenth century. The church is constituted by the nave, the chancel, the sacristy and the corridor to access the pulpit. The walls were built in irregular masonry stone with different thickness. The walls also have eight buttresses with different geometry. The church has been object of several rehabilitation works, which can be grouped into two main groups interventions spaced about 130 years: (a) Interventions carried out between 1775 and 1840; (b) Interventions performed in 1973. During the first period, and due to infiltration of rainwater, minor repairs were made, such as replacement of tiles. These studies were performed with use of materials compatible with the existing ones. In the second period of the works (1973) the General Directorate of National Buildings and Monuments (DGEMN) carried out the reconstruction of the roofs. Currently, the church is not in use and presents severe damage in the vault of the nave and cracks with moderate severity in the transversal walls. The external floor has damage due to the soil settlements. Besides the structural damage, the church has other types of anomalies such as moisture stains in the vaults and at the base of the masonry walls, deterioration of interior paintings, detachment of the external plaster walls, deterioration of external paints, the presence of vegetation and damage in the tiles. This study aims at evaluating the structural performance of the church and to identify the main causes of the existing structural damage. This work involved the preparation and calibration of a numerical model of reference and the nonlinear static analysis for the gravitational loads. Furthermore, three aspects that can have influence on the structure damage were considered, namely, the influence of the filling in the vaults, the influence of the structural scheme of the structure of the roof and the soil-structure interaction. The damage was evaluated based on the capacity curves, displacements and principal strains. In general, the results are similar to the crack pattern of the church an allowed to conclude that the damage seems to be related to the horizontal forces caused by the roof on the top of the walls and to the flexibility of the south part of the structure. However, it is recommended to carry out a diagnosis, namely the roof inspection and geotechnical tests, aiming at validating the previous conclusions.
TipoDissertação de mestrado
DescriçãoDissertação de mestrado integrado em Engenharia Civil (área de especialização em Perfil de Estruturas e Geotecnia)
URIhttps://hdl.handle.net/1822/49853
AcessoAcesso aberto
Aparece nas coleções:BUM - Dissertações de Mestrado
ISISE - Dissertações de Mestrado

Ficheiros deste registo:
Ficheiro Descrição TamanhoFormato 
Diana Celina Bueno Cadena.pdfTese7,27 MBAdobe PDFVer/Abrir

Partilhe no FacebookPartilhe no TwitterPartilhe no DeliciousPartilhe no LinkedInPartilhe no DiggAdicionar ao Google BookmarksPartilhe no MySpacePartilhe no Orkut
Exporte no formato BibTex mendeley Exporte no formato Endnote Adicione ao seu ORCID